โพสเมื่อ
ชื่อสินค้า
FC1012-A Control units Conventional
รายละเอียด:
- Compatible with all conventional Siemens detector series
- 2 selectable detector line standards for a wide range of detector compatibility
- 2 or 6 monitored control lines for sirens, strobe lights etc.
- Programmable alarm organization for manned/unmanned operation
- Suitable to collect non-fire related events with non-latching zone option
- 320 event memory with stamped date and time
- Display of alarm delay countdown
- Simple user controls with isolate/test button per zone
- Key code user access with optional key-switch alternative
- Easy on-site configuration
- Polling facility for service information
- Integral capacity for emergency power of up to 72 h
Technical data
Mains supply voltage | |
AC 115/230 V, +10 %/–15 %, 50/60
Hz | |
Power consumption | |
| |
FC1008/12-A/-B/-C/-D/-F | |
25 … 45 VA / optional 20 … 110
VA | |
FC1008-E | |
20 … 110 VA | |
Quiescent current | |
| |
FC1008-A/-B/-C/-D | |
125 mA | |
FC1008-E | |
170 mA | |
FC1008-F | |
180 mA | |
FC1012-A/-B/-C | |
155 mA | |
FC1012-F | |
220 mA | |
Emergency power operating | |
… 12 h / … 30 h / … 72 h | |
Outputs | |
| |
Dry contact Alarm | |
30 V/1 A, NO/NC | |
Dry contact Fault | |
30 V/1 A, NO/NC | |
Fire control relays (optional, 1...6) | |
250 V/10 A, NO/NC | |
Monitored control lines (2 or 6) | |
24 V/500 mA | |
Driver outputs (14 or 18) | |
24 V/40 mA | |
Control inputs (6) | |
Positive potential via dry contact | |
Interfaces | |
VdS peripherals (only FC1008/12-F) | |
Operating temperature | |
0 ….+50 °C | |
Storage temperature | |
–20 ….+60 °C | |
Humidity (no condensation permitted) | |
| |
at T = 25 ±3 °C | |
?95 % rel. | |
at T = 40 ±2 °C | |
93 % rel. | |
Cabinet | |
| |
Dimension (W x H x D) | |
506 x 378 x 125 mm | |
Color metal chassis | |
grey, ~RAL 9006 | |
Color cover FC10xx-A/-B/-C/-D/-E/-F | |
white, ~RAL 9003 | |
Protection category (IEC 60529) | |
IP40 | |
Standards | |
EN 54-2, EN 54-4 | |
คำค้นหา:
systems conventional fire alarm