โพสเมื่อ
ชื่อสินค้า
FC1004-A Control units Conventional
รายละเอียด:
- Compatible with all conventional Siemens detectors
- 2 selectable detector line standards for a wide range of detector compatibility
- 2 monitored control lines for sirens, strobe lights etc.
- Programmable alarm organization for manned/unmanned operation
- Suitable to collect non-fire related events with non-latching zone option
- Simple user controls with isolate/test button per zone
- Key code user access with optional key switch alternative
- Easy on-site configuration
- Integral capacity for emergency power of up to 72 h
- Battery 7.2 Ah (2 x 12 V)
Technical Data
Supply voltage | |
AC 115/230 V, +10 %/–15 %, 50/60 Hz | |
Power consumption | |
13 ... 25 VA | |
Quiescent current | |
| |
FC1004-A/-B/-C/-E | |
90 mA | |
Emergency power operating | |
… 72 h | |
Outputs | |
| |
Dry contact Alarm | |
30 V/1 A, NO/NC | |
Dry contact Fault | |
30 V/1 A, NO/NC | |
Fire control relays (optional, 1…2) | |
250 V/10 A, NO | |
monitored control lines (2) | |
24 V/500 mA | |
Driver outputs (5 or 7) | |
24 V/40 mA | |
Control inputs (3) | |
Positive potential via dry contact | |
Operating temperature | |
0 … +50 °C | |
Storage temperature | |
–20 … +60 °C | |
Humidity (no condensation permitted) | |
| |
at T = 25 ±3 °C | |
?95 % rel. | |
at T = 40 ±2 °C | |
93 % rel. | |
Cabinet | |
| |
Dimensions (W x H x D) | |
370 x 286 x 90 mm | |
Color cover FC10xx-A/-B/-C/-E | |
white, ~RAL 9003 | |
Protection category (IEC 60529) | |
IP40 | |
Standards | |
EN 54-2, EN 54-4
| |
คำค้นหา:
systems conventional fire alarm