02 949 8472 , 086-339-0213
โพสเมื่อ
ชื่อสินค้า
Honeywell RA890 BURNER CONTROL
รายละเอียด:
Overview
Primary control provides solid state, electronic flame safeguard protection for industrial and commercial single or dual fuel burners for rectification type flame detection.
Features
- Uses rectification principle of electronic flame detection.
- Replaces RA890E in most applications and mounts on same Q270A1024 Subbase.
- Recycles if flame signal lost while in Run. Failure to establish pilot results in a lockout.
- Safe-start check prevents start-up if flame-simulating failure occurs in flame detector circuit.
- Includes built-in protection against ignition crossover in flame rod systems.
- Includes SPDT alarm contacts.
- Solid state circuitry.
- Mounts and removes easily through use of captive mounting screws.
- Mounting base is made of strong thermoplastic.
Product Specifications- Application
- Primary control for rectification application (Flame Rod for example)
- Dimensions (in.)
- 5 in. high x 5 in. wide x 4 3/4 in. deep (including subbase)
- Dimensions (mm)
- 127 mm high x 127 mm wide x 121 mm deep (including subbase)
- Temperature Range (F)
- 60 Hz models -20 F to +115 F,50 Hz models -20 F to +105 F
- Temperature Range (C)
- 50 Hz Models -29 C to +41 C,60 Hz Models -29 C to +46 C
- Frequency
- 50 Hz; 60 Hz
- Approvals, Underwriters Laboratories Inc.
- UL Listed: 120V models only; File No. MP268, Guide No. MCCZ
- Approvals, CSA
- CSA Certified: 120V models only; File No. LR1620
- Voltage
- 220 Vac
- Flame Failure Response Time (sec)
- 0.8 sec
- Safety Switch Timing
- 15 seconds
- Alarm Relay Switching
- SPDT
- Approvals, Factory Mutual
- Approved: Report No. 17678,19417,19784
คำค้นหา:
relay honeywell ra890 burner control protector