[Introduction]
DA-100 detects combustible or toxic gas leakage and transmits standard electric current output signal 4 ~ 20mA to be connected with various controllers such as gas leakage warning device (GMS-1000/1500/2000), PLC, DDC, or MMR for individual or integrated gas monitoring system.
[Features]
Ø Digital Process: built-in micro-processor offers various artificial intelligence functions for more convenient operation and maintenance.
Ø Auto-Calibration: digital process enables one person auto calibration by one-touch (zero calibration and span calibration).
Ø 4-20mA Transmitter: standard electric current output signal (4-20mA) enables a stable transmission even in long distance up to 2.5km.
[Specification]
Detection principle | |
Catalytic, electro-chemical, NDIR, or PID | |
Gas sampling | |
Diffusion | |
Measurement range | |
0 ~ 100%LEL, 0 ~ 10,000ppm, 0 ~ 100%VOL | |
Target gas | |
Combustible or toxic - see the table of target gases | |
Response time | |
Within 20 seconds, 90%/full scale | |
Accuracy | |
?±2%/full scale | |
Calibration | |
One-touch auto calibration | |
Sensor displacement | |
Zero calibration: ?±2%LEL/6 month
span calibration: ?±2%LEL/6 month | |
Self diagnosis | |
Display sensor failure on built-in FND(S.Er), 2mA output | |
Input power | |
DC 20 ~ 30V | |
Output signal | |
4 ~ 20mA/full scale – up to 2.5km transmission | |
Operating temp. & humidity | |
-20?~ 50?, 5 ~ 95% RH (Non-Condensing) | |
Signal cable | |
CVVS & CVVSB 1.25sq x 3 Wire - Shield Type | |
Conduit tube | |
1/2" or 3/4" PF, NPT | |
Installation type | |
Wall or Pipe Mounting | |
Casing material | |
Cast aluminum alloy | |
Explosion-proof approval | |
Ex d IIC T5 | |