รายละเอียด:
CONVENTIONAL INSTALLATION OF ELECTRIC FIRE PUMP AND DIESEL-ENGINE GENERATOR SET:
When the fire occurs, electricity is forced to shut-down, ATS auto-switch to diesel engine generator set ,to produce power to electric Fire pump for operation. Normally, the diesel generator set is stand-by type, for emergency power supply once the electricity is shut-down. It offers emergency power to electric fire pump, elevator, Smoke extraction equipment,emergency lighting,...etc.
FIRE PUMP WITH EVERGUSH DIESEL ENGINE GEN-SET AND ATS
When the installation place is lack of power, or is remote island or mountain. For Fire equipment, FFE-series Diesel engine Fire-fighting pump set is good choice. It's diesel engine driven, can operate by diesel fuel. No need electricity and extra diesel engine gen-set to offer power to fire pump.
Working Conditions:
1.Ambient temperature: Max.40?
2.Liquid temperature: 0~60?
3.It is suitable for clean water or non chemical property liquid. It should not contain solid particles in the liquid.
4.Working pressure: 10~20Bar (Different water pumps withstand different pressure resistance.)
Specification:
1.Rated Power: 29,42,70,76KW
2. RPM: Max.3000 rpm.
3. Factory Pre-set RPM is 2750~2850RPM
4. Head: Max. 96M
5. Rated Flow rate:500~1920LPM
5. Starting Voltage: 12V
6. Fuel Consumption: 7.9~20 Liter/Hr
7. Inlet/Outlet: 4" or 6" or other size.