Room Temperature Sensors
- Passive sensors for acquiring the temperature in rooms.
- Range of use 0...50
๐C / <85% r.h.
Use: In heating, ventilation and air conditioning plants for acquiring the room temperature
Type summary:
- QAA2010 Pt100 0...50
๐C Approx. 7 min
- QAA2012 Pt1000 0...50
๐C Approx. 7 min
- QAA2040 T1 0...50
๐C Approx. 7 min
- QAA2030 NTC 10k 0...50
๐C Approx. 7 min
Equipment combinations:
The room temperature sensors are suited for use with all types of controllers that can handle analog, passive sensor signals.
Technical data:
Functional data
Range of use: refer to "Type summary"
Sensing element: refer to "Type summary"
Time constant: refer to "Type summary"
Measuring accuracy: refer to "Function"
Type of measurement and output: passive
Protective data
Degree of protection: IP 30 to IEC 529
Safety class: III to EN 60730
Electrical connections
Screw terminals for: 2 x 1.5 mm
2 or 1 x 2.5 mm
2
Perm. cable lengths: refer to "Engineering notes"
Environmental conditions
Operation: to IEC 721-3-3
Climatic condition: class 3K5
Temperature: 0...50
๐C
Humidity: <85% r.h.
Transport: to IEC 721-3-2
Climatic condition: class 2K3
Temperature: -25...+65
๐C
Humidity: <95% r.h.
Mechanical environmental conditions: class 2M2
Materials and colors
Housing front: ASA+PC, NCS S 0502-G (withe)
Bottom: ASA+PC, NCS 2801-Y43R (grey)
Base: PC, NCS 2801-Y43R (grey)
Packaging: corrugated cardboard
Sensor (complete assembly): silicone-free
Incl. packaging: Ca. 0,1 kg