FLEXmax Specifications | |
| |
| |
| |
| |
FLEXmax 80 - FM80-150VDC | |
FLEXmax 60 - FM60-150VDC | |
Nominal Battery Voltages | |
12, 24, 36, 48, or 60 VDC (Single model - selectable via | |
12, 24, 36, 48, or 60 VDC (Single model - selectable via | |
Maximum Output Current | |
80 amps @ 104º F (40ºC) with adjustable current limit | |
60 amps @ 104º F (40ºC) with adjustable current limit | |
Maximum Solar Array STC Nameplate | |
12 VDC systems 1250 Watts / 24 VDC systems 2500 Watts / | |
12 VDC systems 900 Watts / 24 VDC systems 1800 Watts / | |
| |
| |
48 VDC systems 5000 Watts / 60 VDC Systems 7500 Watts | |
48 VDC systems 3600 Watts / 60 VDC Systems 4500 Watts | |
NEC Recommended Solar Array STC Nameplate | |
12 VDC systems 1000 Watts / 24 VDC systems 2000 Watts / | |
12 VDC systems 750 Watts / 24 VDC systems 1500 Watts / | |
| |
| |
48 VDC systems 4000 Watts / 60 VDC Systems 5000 Watts | |
48 VDC systems 3000 Watts / 60 VDC Systems 3750 Watts | |
PV Open Circuit Voltage (VOC) | |
150 VDC absolute maximum coldest conditions / 145 VDC | |
150 VDC absolute maximum coldest conditions / 145 VDC | |
| |
| |
start-up and operating maximum | |
start-up and operating maximum | |
Standby Power Consumption | |
Less than 1 Watt typical | |
Less than 1 Watt typical | |
Power Conversion Efficiency | |
97.5% @ 80 Amps in a 48 VDC System - Typical | |
98.1% @ 60 Amps in at 48 VDC System voltage - Typical | |
Charging Regulation | |
Five Stages: Bulk, Absorption, Float, Silent and Equalization | |
Five Stages: Bulk, Absorption, Float, Silent and Equalization | |
Voltage Regulation Set points | |
10 to 60 VDC user adjustable with password protection | |
10 to 60 VDC user adjustable with password protection | |
Equalization Charging | |
Programmable Voltage Setpoint and Duration - Automatic | |
Programmable Voltage Setpoint and Duration - Automatic | |
| |
| |
Termination when completed | |
Termination when completed | |
Battery Temperature Compensation | |
Automatic with optional RTS installed / 5.0 mV per °C per | |
Automatic with optional RTS installed / 5.0 mV per °C per | |
| |
| |
2V battery cell | |
2V battery cell | |
Voltage Step-Down Capability | |
Can charge a lower voltage battery from a higher voltage | |
Can charge a lower voltage battery from a higher voltage | |
| |
| |
PV array - Max 150 VDC input | |
PV array - Max 150 VDC input | |
Programmable Auxilary Control Output | |
12 VDC output signal which can be programmed for different | |
12 VDC output signal which can be programmed for different | |
| |
| |
control applications (Maximum of 0.2 amps DC) | |
control applications (Maximum of 0.2 amps DC) | |
Status Display | |
3.1” (8 cm) backlit LCD screen - 4 lines with 80 alphanumeric | |
3.1” (8 cm) backlit LCD screen - 4 lines with 80 alphanumeric | |
| |
| |
characters total | |
characters total | |
Weight | |
Unit | |
12.20 lbs (5.56 kg) | |
11.65 lbs (5.3 kg) | |
| |
Shipping | |
15.75 lbs (7.10 kg) | |
14.55 lbs (6.4 kg) | |
Dimensions | |
Unit | |
16.25” x 5.75” x 4” (41.3 x 14 x 10 cm) - (H x W x D) | |
13.5 x 5.75 x 4” (40 x 14 x 10 cm) | |
| |
Shipping | |
21” x 10.5” x 9.75” (53 x 27 x 25 cm) | |
18 x 11 x 8” (46 x 30 x 20 cm) | |
Certifications | |
| |
ETL Listed to UL1741, CSA C22.2 No. 107.1 | |