โพสเมื่อ
ชื่อสินค้า
FC1820-A1 Fire Alarm Controller (252 points)
รายละเอียด:
- Multi-language operation menu designed Windows-like for fast and easy operation
- Shortcut key (right key) for popping out operation items of equipment/event
- Large history storage size for up to 10,000 records, first-in-first-out order; all events can be recorded during operation period
- LCD backlight Auto-off mode. When no operation or message to display within preset time, LCD backlight will automatically turn off. When there are events /operations, LCD will light up automatically to display events and/or interlock devices
- 2 channels of programmable input/output (Output: 40mA@24VDC can be programmed as general alarm output or general trouble output; Input: dry contact)
- 1 channel of NAC for audible and visible devices (max. 0.5A @24VDC)
- 8 channels of interlocking functions for automatic control and manual operations of control equipment
- Efficient group programming according to different usage
- FC1820 controller can connect up to 252 points
- Up to 32 controllers can be networked together
- Max. distance of controller network bus (FC18-BUS) 1,000m
- Twisted paired cable for polarity-free detection bus (FD18-BUS); max. loop distance up to 2,500m, and max. stub distance up to 1,500m (wiring capacity from 1.0 to 1.5 mm2 )
- Three user levels for different operation authority. Each user level accessed by pre-defined, changeable password
- Convenient pluggable terminals with clear marks for field wiring
- Auto-mapping function supports commissioning task
- Detection algorithm can be adjusted by controller according to different environment to provide high reliability of alarm report and reduce false alarms
- Programming either directly from controller or computer
- “Sticker Method” for ease of on-site commissioning
- FD18-BUS detection bus can be configurated as loop or stubs
- FC18-BUS controller bus can be configurated as stub
Technical data
No. of line cards | |
1 | |
Number of points | |
252 | |
LCD screen | |
320×240 pixels, backlit | |
No. of programmable input/output on main board | |
2 | |
No. of zone of interlocking panel | |
8 | |
No. of NAC (0.5mA @24VDC) | |
1 | |
Maximum history records | |
10,000 | |
Max. distance between controllers within FC18-BUS | |
1,000 m | |
Max. No. of controllers connected within FC18-BUS | |
32 | |
Max. distance between controller and FRT within FR18-BUS | |
1,000 m | |
Max. No. of FRT connected to controller | |
32 | |
Auto-mapping function | |
Operation from terminal | |
Battery (not included) | |
Depends on local regulation | |
Communication interface | |
Special converter module | |
Input voltage | |
220VAC@ 1.5A, 110VAC@3A | |
| |
220VAC/50Hz, 110VAC/60Hz | |
Power supply capacity | |
5 A@24 VDC | |
External power output | |
1 A@24 VDC | |
Size (mm) | |
437Wx 408Hx170D | |
Weight (without battery) | |
10.35 kg | |
Power fuse | |
220VAC@ 1.5A, 110VAC@3A | |
Battery fuse | |
24 [email protected] A | |
Operating temperature | |
0 ~ +40 ?C | |
Storage temperature | |
–10 ~ +50 ?C | |
Relative humidity | |
? 95% (40±2°C) | |
Protection category | |
IP30 | |
Environment requirement | |
Indoor / Clean | |
Datasheet | |
A6V10322968 | |
คำค้นหา:
systems addressable fire alarm